FL(R) N36-12D-indoor High-voltage SF6 Switches
FL(R) N36-12D-indoor High-voltage SF6 Switches

GENERAL

FL (R) N36-12D-indoor high-voltage SF6 Switches is the rated voltage 12 kV indoor switching equipment, used SF6 gas as an interrupter and insulated medium, including closing, the gate and grounding the three-position, have small volume , Easy to install and adaptable to the environment characteristics.
FL (R) N36-12D-indoor high-voltage SF6 load switches and other electrical components combints, to achieve control and protection, as a secondary substation control and protection in industrial and mining enterprises, civilian power supply and electrical equipment. FLRN36-12D Switches - fuse combinations matches transformer protection apply to the Central net power supply unit particularly.

MAIN FEATURES
FLN36-12D/T630-20 indoor high-voltage SF6 load switch (hereinafter referred to Switches) and FLRN36-12D/T125-31.5-Switches - fuse combinations (the combinations) in line with national standards GB3804-2004 "3.6 ~ 40.5kV high voltage Switches "(eqvIEC60265-1: 1997) and GB16926-1997" exchange of high-pressure Switches - fuse combinations "(eqvIEC420: 1990).

MAIN TECHNICAL PARAMETERS

No.

Name

Unites

Data

FLN36-12D/T630-20
Load switcher

FLRN36-12D/T125-31.5
Load switcher—Fuse combinations

1

Ratedvoltage

kV

12

2

Ratedfrequency

Hz

50

3

Ratedcurrent

A

630

125

4

Ratedinsulation level

1 minFrequencytolerance voltage

kV

In contrast, the 42-and 48 fracture

Lightningshock tolerance voltage

kV

In contrast, the 75and 85 fracture

underthe zero table tolerance rated voltage

kV

12

5

Ratedthermal stability current(3S)

kA

20

6

Rateddynamic stability current

kA

50

7

Ratedshort-circuit the Commissioner of current

kA

50

80(Expected)

8

Ratedclosed-loop breaking current

A

630

9

Ratedmeritorious breaking load current

A

630

10

Ratedcable breaking current charge

A

10

11

Groundfault current

A

5

12

Underthe conditions of the fault lines and cables the charge current

A

20

13

Ratedshort-circuit breaking current

kA

31.5(Expected)

14

Ratedtransfer current

A

1700

15

Fusetypes

SKLDJ-12/125A*

16

Impactof output energy

J

1±0.5

17

Thermalstability of the earth switch rated current(3S)

kA

20

18

Dynamicstability of the earth switch rated current (peak)

kA

50

19

Commissionerof the earth switch rated short-circuit a current

kA

50

20